Save valuable rack space and generate more revenue: The NetGuardian 480 has 80 discrete point inputs, 4 control relays, and an optional D-wire input supporting up to 16 analog sensors.
Find temperature, humidity, and many other
discrete and analog sensors for your DPS RTUs.
| Full Specifications | |
|---|---|
| Discrete Inputs: | 80 |
| Ping Targets: | 16 |
| Alarm Detection Speed: | Configurable to 100-9000 msec (1/10 second to 9 seconds) |
| Control Outputs: | 4 (Form C) |
| Maximum Voltage: | 60 VDC/125 VAC |
| Maximum Current: | 0.5 Amp, 125 VAC 1 Amp, 24 VDC |
| Protocol: | TL1 SNMP v1, v2c DCPx (all versions) TELNET HTTP TAP ICMP |
| Interfaces: | Two 50-pin connectors for discrete alarms and control relays 1 RJ45 10/100BaseT Ethernet Port 1 USB Craft Port 1 Serial Port (Choose from RS232, RS485, 202, or 33.6K Dialup Modem) (Optional) 1 D-Wire sensor input supporting up to 16 analog sensors |
| Power Input: | -48VDC (-36 to -72VDC) (Optional) -24VDC (-18 to -36VDC) (Optional) 130VDC (Optional) +24VDC via 110VAC wall transformer (+12 to +30VDC) |
| Current Draw: | 250 mA |
| Fuse: | 3/4 AMP GMT |
| Visual Display: | 6 Front Panel LEDs 1 Rear Panel LED |
| Mounting: | 19" or 23" rack |
| Dimensions: | 1.72" H x 17" W x 5.14" D |
| Weight: | 4 lbs. 3oz. (1.9 kg) |
| Operating Temperature: | 32 -140 degrees F (0 -60 degrees C) |
| Operating Humidity: | 0%-95% non-condensing |
Give Us a Call!
To find out more about this and other DPS applications, give us a call at our toll-free number and talk to one of our network specialists. They'll help you put together a perfect fit solution for your network!
Sales: 1-800-693-0351 · Fax: 559-454-1688