2354

NetGuardian 832A G5 Specs

NetGuardian 832A G5 Back Panel
The NetGuardian 832A monitors 32 discrete alarms and 8 analog alarms, pings 32 network elements, controls 8 relays, provides LAN reach through access to 8 serial ports, and reports via SNMP v2c or DCPX, e-mail, or pagers

Full Specifications.
Protocols: SNMPv1, SNMPv2c, SNMPv3 or DCP (depending on firmware ordering options), SNPP, TAP (Alpha) paging, Numeric paging, SMTP (Email), and HTTP (Web).
Discrete Inputs: 32 (expandable to 80, 128 or 176 see options).
Alarm Detection Speed: User-defined (3 to 999 msec).
Analog Inputs: 8.
Analog Input Range: (-92 to 92 VDC or 4 to 20 mA).
Analog Accuracy: +/- 1% of actual value.
D-Wire Sensors: 16
Control Outputs: 8 Form C relay contacts (expandable to 16, 24, 32).

Max Voltage:

60 VDC/120 VAC.

Max Current:

1 Amp, AC/DC.
Terminal server ports: Up to 8.
IP Address Ping Targets: 32
Interfaces:

8 RJ45 YOST standard RS-232 ports (see options).
2 RJ45 10/100BaseT Ethernet port.
1 RJ11 Telco jack.
2 50-pin amphenol connectors (discretes, controls, and analogs).
1 4-pin screw connector (analogs).
1 Optional. D-Wire sensor port

Modem: 33.6K internal.
Visual Interface:

LCD display with descriptive text
18 bicolor LEDs.
5 unicolor LEDs (11 with Switch Option).

Audible Interface: Alarm speaker
Dimensions: 1.75"H x 17"W x 12"D
(4.5 cm x 43.2 cm x 30.5 cm)
Weight: 4 lbs. 3 oz. (1.9 kg)
Mounting: 19" or 23" rack
Power Input: -48VDC (-40 to -56 VDC) see options
(Optional) -24 VDC (-20 to -56 VDC)
(Optional) Wide Range -24/-48 VDC (-20 to -56 VDC)
(Optional) 130 VDC
Current Draw: 200mA
Power Output: (Optional) 12 VDC or 24 VDC @ 1 amp (maximum) for external Power sensor.
Fuse: 3/4 Amp GMT for power inputs
3/4 Amp GMT for external sensor power outputs and integrated Ethernet Switch.
Operating Temperature: 32 to 140 F (0 to 60 C)
Extended Operating Temperature: (Optional) -22 to 158 F (-30 to 70 C)
Operating Humidity: 0%-95% noncondensing
RoHS 5 Approved Yes

Pinouts

NetGuardian 832A G5 Back Panel
NetGuardian 832A Pinouts.
RJ45 Ethernet Connection RJ11 Phone Line Connection


Get a Custom Application Diagram of Your Perfect-Fit Monitoring System

There is no other network on the planet that is exactly like yours. For that reason, you need to build a monitoring system that's the right fit for you.

"Buying more than you need" and "buying less than you need" are real risks. You also have to think about training, tech support, and upgrade availability.

Send me a quick online message about what you're trying to accomplish. I'll work with you to build a custom PDF application diagram that's a perfect fit for your network.


Make an Informed Decision


Your network isn't off-the-shelf.

Your monitoring system shouldn't be, either.

Customized monitoring application drawing

We'll walk you through this with a customized monitoring diagram.

Just tell us what you're trying to accomplish with remote monitoring.

Get a Custom Diagram